Hapuflam® fire protection mortar
for cable fire stops
Classification | S90 according to DIN 4102 |
---|---|
Approval number | Z-19.15-1560 |
Installation | square cable fire stops in solid walls and ceilings |
Product description
Hapuflam® fire protection mortar is a dry ready mortar containing all necessary binders and aggregates in its base mass. The consistency of the ready fire protection mortar can be moulded and therefore also inserted as a filler without casing.
Our Hauflam® fire protection mortar is particularly suited to wall and ceiling openings where the filler thickness is just 20 cm
Installation instructions
The prepared Hapuflam® fire protection mortar can be inserted by hand or, for larger recesses, using a mortar pump and lance.
Wall thicknesses | Max. filler size | Min. filler depth |
---|---|---|
Masonry > 100mm | 1200 x 2500 | 200 mm |
Concrete /reinforced concrete > 100mm | 1200 x 2500 | 200 mm |
Light partition wall > 100mm | 1200 x 2500 | 200 mm |
Ceiling thicknesses | max. partition size | min. partition size |
---|---|---|
Concrete /reinforced concrete > 160mm | 1000 x ∞ | 200 mm |
Allocation
Supply container
- Bucket with 12 kg contents of drying mortar
- Sack goods, contents approximately 20 kg of dry mortar
Mixing 20 kg of dry mortar with approximately 15 L of water results in a container of approximately 34 L of ready fire protection mortar.
Mix ratio for small quantities:
1.00 litre dry mortar
+ 0.37 litre water
= 0.82 litre wet mortar